[caldera_form id=”CF5bdc5e6d26ec8″]
APT Floor-Standing Generator Linkboard Panel provides a simplified means of reconnecting the 12 lead generator for either low voltage mode (240-208V L-L / 120V L-N) or high voltage mode (480V L-L / 277V L-N) operation. APT Floor-Standing Generator Linkboard Panel consists of a base insulating board with copper bus bars installed and a movable top insulating board with various copper bus bar links installed. Voltage changeover is achieved by removing Linkboard nuts/washers, moving the Linkboard up or down a position as required, and then reinstalling the nuts/washers. Limit switches shall sense the Linkboard position and illuminate a corresponding indicating lamp on the door.